Sound insulation is commonly quantified using the Sound Reduction Index (SRI), R.
Where:
Standard | Description |
---|---|
ISO 140-3 | 100-3150 Hz |
ASTM E90 | 125-4000 Hz |
EN/ISO 10140-3 | Attempt to extend the range in low-frequency region down to 50 Hz third octave band |
Note: It is advised to perform the specimen (wall, roof or floor sample) using dimensions as close as possible to the dimensions used in project. Using smaller dimension tends to overestimate the performance low-frequency range.
The effect of a doubling is characterized by the sound reduction improvement index, ΔR which is defined as:
Where:
Note:
Direction transmission that is characterized by sound reduction index, R is not the sole factor that affects the sound insulation between 2 spaces. Flanking transmission is the transmission of sound by walls or floors linked to the separating element. Whereas, parasite transmission is the sound leakage around a contructive element or through a duct or opening. Figure 1 below illustrates few transmission paths between 2 spaces.
Figure 1: Direct and Flanking Transmission between Rooms (Source: [1])
To quantify the overall contribution of all the factors mentioned, the sound insulation between rooms is also commonly characterized using the sound level difference, D:
However, the sound insulation value is dependent on the amount of acoustic absorption inside the receiving room. Therefore, the usual rule is to standardize the result by the reverberation time. Which gives the standardized sound insulation, DnT:
Where:
Standard | Description |
---|---|
ISO 140-4 | 100-3150 Hz |
ASTM 336 | 125-4000 Hz or 100-5000 Hz (France) |
EN/ISO 16283-1 | Attempt to extend the range in low-frequency region down to 50 Hz third octave band |
The effect on the sound field of a slightly leaky room is shown in Figure 2 below.
Figure 2: Example of Sound Intensity Contours Benhind a Window, Either Closed (Left) or Slightly Opened (Right) (Source: [1])
To speed up the rating of specimens, experts usually rely on single number rating. It is an obvious simplification compared to the usual 6 octave bands (125-4000 Hz). ASTM had came up with the Sound Transmission Class (STC) which features a sliding contour. The contour runs 9 dB per octave from 125 to 500 Hz, 3 dB per octave from 500 to 1250 Hz and stays flat from 1250 to 4000 Hz.
To determine the STC value, one glides the contour over the sound reduction or sound insulation curved measured until the sum of negative deviations is no greater than 32 dB and the maximum negative deviation is 8 dB. Whereas ISO uses the R_w or D_w system, which is similar but the frequency range is 100 to 3150 Hz. To cope with low frequencies down to 50 Hz, ISO has extended its R_w contour in standard ISO 16717-1.
The most fundamental and crudest model is the mass law.
Where:
There are a few computer programs available to try to compute the sound insulation between rooms. Such programs rely on the knowledge of the sound reduction index of the various walls, as well as their coupling parameters, and operate according to ISO 12354. Most of the time they come with a rather significant database.
The noise radiated by a building will depend on the sound reduction index of each envelop componenet as well as respective area.
Where:
[1] M. Asselineau, Building Acoustics. Boca Raton, Florida: CRC Press, 2015.
[2] D. A. Bies, C. H. Hansen, and C. Q. Howard, Engineering Noise Control, 5th ed. Boca Raton, Florida: CRC Press, 2017.